Wire & Cable Color Code Chart
The ICEA Method 1 conductor color sequences for multi-conductor cable: Table E-1 (21 conductors) and Table E-2 (36 conductors), with visual swatches for every base color and tracer combination, plus the standard building wire color conventions.
How Cable Color Coding Works
Multi-conductor cables built to ICEA S-73-532 (NEMA WC57) identify each conductor one of four ways. Method 1, colored insulation with tracer stripes, is what the charts below cover. Method 2 uses a neutral-colored compound with colored tracers in the same sequence, Method 3 uses colored braids, and Method 4 prints a number on black insulation, which is what you'll find on most modern tray and control cable.
In every case, conductor 1 sits at the center of the assembly and the count works outward through the layers. Solid colors come first; once they're used up, the sequence repeats each base color with a contrasting tracer stripe.
ICEA Table E-1 (21 Conductors)
Table E-1 uses six base colors including white and green. You'll see it on instrumentation and signal cable where the conductors don't land in an NEC branch-circuit context.
| # | Color | Base / Tracer | # | Color | Base / Tracer |
|---|---|---|---|---|---|
| 1 | Black | 12 | Black / White tracer | ||
| 2 | White | 13 | Red / White tracer | ||
| 3 | Red | 14 | Green / White tracer | ||
| 4 | Green | 15 | Blue / White tracer | ||
| 5 | Orange | 16 | Black / Red tracer | ||
| 6 | Blue | 17 | White / Red tracer | ||
| 7 | White / Black tracer | 18 | Orange / Red tracer | ||
| 8 | Red / Black tracer | 19 | Blue / Red tracer | ||
| 9 | Green / Black tracer | 20 | Red / Green tracer | ||
| 10 | Orange / Black tracer | 21 | Orange / Green tracer | ||
| 11 | Blue / Black tracer |
Conductor 1 is at the center of the assembly. Sequence per ICEA S-73-532 / NEMA WC57, Method 1, Table E-1.
ICEA Table E-2 (36 Conductors)
Table E-2 drops white and green from the palette so that no conductor can be confused with a neutral or an equipment ground, substituting yellow and brown. It's the sequence most often specified for control cable in NEC installations, and it extends to 36 conductors.
| # | Color | Base / Tracer | # | Color | Base / Tracer |
|---|---|---|---|---|---|
| 1 | Black | 19 | Orange / Blue tracer | ||
| 2 | Red | 20 | Yellow / Blue tracer | ||
| 3 | Blue | 21 | Brown / Blue tracer | ||
| 4 | Orange | 22 | Black / Orange tracer | ||
| 5 | Yellow | 23 | Red / Orange tracer | ||
| 6 | Brown | 24 | Blue / Orange tracer | ||
| 7 | Red / Black tracer | 25 | Yellow / Orange tracer | ||
| 8 | Blue / Black tracer | 26 | Brown / Orange tracer | ||
| 9 | Orange / Black tracer | 27 | Black / Yellow tracer | ||
| 10 | Yellow / Black tracer | 28 | Red / Yellow tracer | ||
| 11 | Brown / Black tracer | 29 | Blue / Yellow tracer | ||
| 12 | Black / Red tracer | 30 | Orange / Yellow tracer | ||
| 13 | Blue / Red tracer | 31 | Brown / Yellow tracer | ||
| 14 | Orange / Red tracer | 32 | Black / Brown tracer | ||
| 15 | Yellow / Red tracer | 33 | Red / Brown tracer | ||
| 16 | Brown / Red tracer | 34 | Blue / Brown tracer | ||
| 17 | Black / Blue tracer | 35 | Orange / Brown tracer | ||
| 18 | Red / Blue tracer | 36 | Yellow / Brown tracer |
Conductor 1 is at the center of the assembly. Sequence per ICEA S-73-532 / NEMA WC57, Method 1, Table E-2.
Building Wire Color Conventions (NEC Systems)
Single-conductor building wire follows a different set of rules. The NEC only mandates a few of them: grounded neutrals must be white or gray (NEC 200.6), equipment grounds must be green, green/yellow, or bare (NEC 250.119), and the high leg of a delta system must be orange (NEC 110.15). The phase colors below are near-universal North American convention:
| Conductor | 120/240V & 120/208V | 277/480V |
|---|---|---|
| Phase A | Black | Brown |
| Phase B | Red | Orange |
| Phase C | Blue | Yellow |
| Neutral | White | Gray |
| Equipment ground | Green, green/yellow stripe, or bare copper | |
Phase colors are industry convention, not code, except where noted. Panel shops wiring to NFPA 79 machine standards use a different scheme again (e.g., red for AC control, blue for DC control, yellow for foreign-voltage circuits).
Frequently Asked Questions
Which table does my cable use?
Check the cable's spec sheet. As a rule of thumb: instrumentation and signal cable often uses E-1, control and tray cable is usually E-2 or printed numbers (Method 4). When ordering, specify the table if conductor identification matters to your termination drawings.
What's a tracer?
A thin contrasting stripe applied along the conductor insulation. Once the solid base colors are used up, the sequence repeats each base color with a tracer, so "red with black tracer" is a different conductor than plain red.
Why does Table E-2 skip white and green?
In NEC installations, white and gray identify grounded neutrals and green identifies equipment grounds. Omitting them from the control-cable palette removes any chance of a phase or control conductor being mistaken for either one.
Can I get custom colors or striping?
Yes. Most of our hook-up wire and multi-conductor lines are available with custom colors, stripes, and ID printing. Tell us the color schedule when you request a quote.