Copper and aluminum carry nearly all of the electrical power in North America. Copper is the default for branch circuits, controls and anything that flexes. Aluminum dominates overhead lines and underground distribution, and it shows up in many building services and feeders. This guide covers the material differences that drive those choices: conductivity, weight, alloys, terminations and where each metal is used.
If you're sizing a specific feeder or service and comparing cost, go straight to our copper vs aluminum building wire guide, which has an equivalent-size table by amperage.
Quick Comparison
| Property | Copper | Aluminum |
|---|---|---|
| Conductivity (% IACS) | 100% (annealed copper is the reference) | About 61% (1350 and AA-8000 alloys) |
| Density | 8.89 g/cm³ | 2.70 g/cm³ (about 30% of copper) |
| Area needed for equal resistance | Baseline | About 1.6×, roughly two AWG sizes larger |
| Weight at equal resistance | Baseline | About half |
| Thermal expansion | About 17 ppm/°C | About 23 ppm/°C (roughly 40% more) |
| Melting point | 1,085°C (1,985°F) | 660°C (1,220°F) |
| Surface oxide | Thin and easy to break through at a connection | Hard, electrically insulating, and re-forms within seconds of exposure to air |
| Creep under clamping pressure | Low | Higher; AA-8000 alloys greatly reduce it |
| Flex and fatigue life | Better | Breaks sooner under repeated bending or nicks |
| Common ASTM standards | B3 (soft wire), B8 (stranded), B33 (tinned) | B800/B801 (AA-8000 building wire), B230/B231 (1350 for overhead) |
Conductivity and Conductor Size
Conductivity is measured against the International Annealed Copper Standard (IACS), where annealed copper is 100%. Electrical-grade aluminum comes in around 61%, so for the same resistance an aluminum conductor needs about 1.6 times the cross-sectional area. Each AWG step changes area by about 26%, which is why the rule of thumb is "go up two sizes for aluminum."
The NEC ampacity tables bake this in. Here is a real pair from the 75°C column of NEC Table 310.16:
| 6 AWG Copper | 4 AWG Aluminum | |
|---|---|---|
| Ampacity, 75°C (NEC Table 310.16) | 65 A | 65 A |
| DC resistance at 75°C (NEC Ch. 9, Table 8) | 0.491 Ω per 1,000 ft | 0.508 Ω per 1,000 ft |
| Stranded conductor diameter | 0.184 in | 0.232 in |
| Bare conductor weight | About 81 lb per 1,000 ft | About 39 lb per 1,000 ft |
At the same ampacity, the aluminum conductor weighs a little less than half as much and has about 3% more resistance. The trade-off is a diameter about 26% larger, which means a bigger insulated wire and possibly a bigger conduit. Always run voltage drop for the material you're actually buying. Our wire size calculator handles both.
Weight, Strength and Handling
Aluminum's light weight is its biggest advantage outside of price. Reels are lighter to ship and handle, and on overhead lines the lower weight per foot allows longer spans with fewer structures. That's why utility lines are almost entirely aluminum, often with a steel or high-strength alloy core for tensile strength.
Copper is stronger and more ductile. It tolerates repeated bending, vibration and the occasional nick far better than aluminum, which is why flexible cords, portable cable, welding cable and machine wiring are copper. Aluminum is perfectly reliable when it's installed once and left alone, the way feeders and services are.
Not All Aluminum Is the Same: Alloys Matter
| Alloy | Where it's used | Notes |
|---|---|---|
| 1350 (EC grade) | Overhead conductors (AAC, the aluminum strands of ACSR), utility and medium-voltage cable | Highest-conductivity aluminum. Also the alloy used in the 1960s–70s solid branch-circuit wiring that gave aluminum its bad reputation. |
| 6201 | AAAC overhead conductor | Heat-treated for strength at some cost in conductivity |
| AA-8000 series | Aluminum building wire: XHHW-2, THHN, RHW-2/USE-2, SER and SEU | Required by NEC 310.3(B) for aluminum building wire. Better creep resistance and thermal-cycling performance at terminations. |
For a closer look at overhead aluminum, see AAC vs AAAC vs ACSR. For underground utility cable, see our 15 kV aluminum URD guide.
On the copper side, building wire uses soft (annealed) copper per ASTM B3 and B8. Tinned copper (ASTM B33) adds corrosion resistance and solderability and is common in marine and flexible cable. Hard-drawn copper (ASTM B1) is used where tensile strength matters, such as some bare overhead conductors.
Copper-clad aluminum (CCA) is an aluminum core bonded to a copper outer layer. The NEC requires the copper to make up at least 10% of the cross-sectional area and the core to be AA-8000 alloy. CCA is not a substitute for solid copper in Category-rated data cable.
Terminations: Where Aluminum Installations Succeed or Fail
Almost every aluminum failure story is a connection story. Aluminum's insulating oxide, higher thermal expansion and tendency to creep all work against a loose or wrong connector. Modern practice handles all three:
- Use terminals rated for aluminum. Lugs and breaker terminals marked AL7CU (75°C) or AL9CU (90°C) accept aluminum or copper. A terminal marked only "CU" is copper-only.
- Devices need CO/ALR. 15 A and 20 A receptacles and switches must be marked CO/ALR to accept aluminum directly.
- Don't mix metals in a connector unless it's identified for it. NEC 110.14 prohibits copper and aluminum touching in a terminal or splice unless the device is identified for the purpose. Most standard twist-on connectors are not.
- Prepare the conductor. Clean or abrade the strands and apply oxide inhibitor wherever the connector manufacturer requires it. Many compression lugs come pre-filled.
- Torque to the marked value. NEC 110.14(D) requires a calibrated torque tool when a torque value is specified. Under- and over-torqued lugs cause problems with copper too, but aluminum is less forgiving.
Where Each Metal Is Used
| Application | Usual choice | Why |
|---|---|---|
| Branch circuits (15–30 A) | Copper | Devices and small terminals are built for copper, and the cost difference is small at these sizes |
| Services and feeders (100 A and up) | Aluminum is common; copper is also used | Savings grow with conductor size. Requires AL-rated lugs and a conduit-fill check. See SER vs SEU. |
| Overhead distribution and transmission | Aluminum (AAC, AAAC, ACSR) | Weight and cost per span |
| Underground distribution (URD) | Mostly aluminum | Cost on long runs |
| Control, motor leads, machine wiring | Copper | Small sizes, vibration, terminal compatibility |
| Flexible cord, portable cable, welding and DLO | Copper (fine-stranded) | Flex life |
| Grounding electrode conductors | Usually copper | NEC 250.64(A) restricts aluminum in contact with earth or masonry and within 18 in. of the earth outdoors |
| Electronics and hook-up wire | Copper | Fine gauges, solderability |
What About the Old Aluminum Wiring Problems?
The problems were real. From the mid-1960s to the mid-1970s, some homes were wired with small solid aluminum branch circuits in an early alloy, connected to switches and receptacles designed for copper. Loose connections overheated. The industry responded with AA-8000 alloys, CO/ALR devices and connectors listed for aluminum. Today aluminum is used mostly in larger stranded feeder and service sizes on AL-rated lugs, which is a very different installation from the one that caused the trouble.
Cost
Copper costs much more per pound than aluminum, and its price moves with the commodity market. Even after upsizing, aluminum is usually the lower-cost choice for large feeders and long runs. At branch-circuit sizes the dollar difference is small and copper's device compatibility wins. Prices move constantly, so compare current quotes for both on any job where aluminum is an option.
Quick Decision Checklist
- Branch circuit to standard devices? Copper.
- Feeder or service 100 A and up? Price both. Aluminum often wins if the equipment lugs are AL-rated and conduit fill works.
- Long run? Check voltage drop for both materials before deciding.
- Flexing, vibration or portable use? Copper.
- Does the project spec require copper? Many industrial and healthcare specs do, so follow the spec.
Code references are to the 2023 NEC. Check the edition and any amendments adopted in your jurisdiction.